Publication: Alternative method for determining cycles of concentration in the industrial evaporative system.
No Thumbnail Available
Date
2025-10
Authors
Tan, Chiat Soon
Journal Title
Journal ISSN
Volume Title
Publisher
Abstract
The Cycles of Concentration (COC) is a critical parameter in the operation of evaporative systems such as boilers and cooling towers, directly impacting efficiency, maintenance, and longevity. This research focused on the industrial sector, leverages the experience of the student with over a decade in water treatment industry. Existing methods for determining COC, which involve measuring Total Dissolved Solids (TDS), silica, chloride, and total alkalinity, often lack precision and practicality for continuous, real-time monitoring. Those existing methods are also laborious and involve multiple procedure such as sample collection, laboratory analysis, and titration. This research aims to develop an alternative method for calculating COC using alkalinity measurements via pH probes, which are cost-effective and facilitate continuous monitoring. The objectives of this study include developing a correlation model for COC based on the pH of feed water and water in boiler/cooling systems and validating this model with industrial data. Data from four palm oil mills in Indonesia and seven cooling tower system in Malaysia were used for testing the evaporative systems of boilers and cooling towers, respectively. Interestingly, the overlapping data points between the two methods of the study suggest that the performance of the alternative method is converging toward that of the existing method. Linear regression analysis for boilers B1 to B4 indicated strong correlations between the two methods, with R² values of 0.8144, 0.9201, 0.8412, and 0.7328, respectively. The linear regression analysis of the COC for cooling towers, CT1 to CT7, comparing the existing chloride-based method against the alternative pH-based method, revealed strong correlations between the two methods. The R² values for the respective cooling towers were 0.9637, 0.9475, 0.9866, 0.9783, 0.9696, 0.9827, and 0.8617. These high R² values supports the validation of the alternative method for COC concentrations across different evaporative systems. The findings reveal that the alternative pH-based method enhances the accuracy of COC determination and supports continuous, automated monitoring, offering a more practical and economical solution compared to traditional techniques. The validated model shows promise in optimizing boiler and cooling system operations, improving water chemistry control, and reducing issues like scaling and corrosion. These improvements are crucial for industrial applications, especially in settings such as Green Buildings, where operational conditions are often challenging.